4012/16 WIRING DIAGRAM, TWIN STARTERS & RELAYS, ELECTRONIC GOVERNOR
(EARLY ENGINES)
4012/16 Diesel, February 1997 6
7
NOTE: To enable engine to run immediately
on depressing start button FPS must be fed
24 volt +ve. To stop break this +ve supply.
On overspeed stopping energise air shutoff
valves also.
All switches shown engine at rest (close on a
fault).
Startinhibit relays allow fuel stop solenoids to
energise before cranking.
Air shutoff solenoid valves micro switches
ensure one valve alone cannot operate (+ve
signal from oil pressure switch).
Key (Fig. 58)
1 Terminal box Perkins supply
2 Starter motor 1
3 Starter motor 2
4 Engine instrument panel
5 Oil temperature
6 Oil pressure
7 Water temperature
8 Oil temperature
9 Oil pressure
10 Water temperature
11 Fuse 2 amp
12 Tachometer
13 Ammeter
14 Emergency stop
15 Start relays
16 Oil pressure switch
17 Charging alternator
18 Start inhibit relays
19 Air shutoff solenoid valves. Energised to
stop on overspeed fault only. Not
continuously rated. Must be manually
reset.
20 Engine fault switches left/right banks
21A Water temp. left
21B Water temp. right
22A Oil pressure left
22B Oil pressure right
23 Fuel stop solenoids (energised to run)
24 Two switch speed unit
25 Switch 2 overspeed
26 Switch 1 700 rpm
27 Magnetic pick-up
28 Engine flywheel
29 Electronic governor control box
30 Electronic governor actuator
31 Speed trim
32 If speed trim pot is not required remove
and correct thus.
33 Typical terminal box
34 Wire sizes
Fig. 58