DIESEL ENGINE DATA
12 4
012/16 Diesel, February 1997
TYPICAL COOLING SYSTEM
* Engine only
*
* Engine with heat exchanger
FUEL SYSTEM
G
OVERNORS
4006 4008
Approved Coolants) See page 21
Total water capacity L
trs Gals Spec Ltrs Gals Spec
200 44 TAG 255 56.1 TAG
232 51 TAG1 316 70 TAG1
232 51 TAG2 316 70 TAG2
185 40 TWG 95 21 TWG*
205 45 TWG2 95 21 TWG2*
82 18 TEG** 108 23.7 TEG**
Max radiator top tank temperature 93°C
Max water temperature into engine 80°C
Thermostat opening temperature 71°C
System pressure 0.5 to 0.7 bar
4012 4016
Approved fuels See
page 20
Minimum size fuel tank 14000 litres (3000 gal.) 18000 litres (
4000 gal.)
Relief valve setting 310 kPA (45 psi)
Inferior nozzle pressure 225-235 atm
Injection equipment Lucas-Bryce unit injector
Filter/water separator Spin-on expandable canister(s)
Fuel lift pump Maximum suction lift 1 metre
Fuel flow 20.457 litre/min. (4.5 gpm) @ 1800 r/min
4012 4016
Type Electronic Electronic
Type Hydraulic Hydraulic
Page view 11